These
apparatus are for heating and cooling of medium and big sized premises, with
direct air throw or distribution by ducts.
|
General features |
-
Double inlet centrifugal fan coupled with electric motor by pulleys and belts;
-
heat exchanger coil made of copper tubes and aluminium fins secured to the
tubes by mechanical expansion, operating with hot water and cold water;
-
water condensates basin collector;
-
aluminium frame and casing made of prepainted galvanized stell, insulated;
-
optionals: plenum for direct air throw with grills made of adjustable air
deflector blades, electrical control board, inductive energy recuperator;
-
pleated air inlet filter regenerable and washable;
-
comply with the EEC Directives n. 73/23, 89/392, 91/368, 93/44, 93/68.
|
Mod. |
TV/TO
2 |
TV/TO
3 |
TV/TO
4.5 |
TV/TO
6 |
TV/TO
9 |
TV/TO
12 |
TV/TO
16 |
Air flow rate |
Mc/h |
2.000 |
3.000 |
4.500 |
6.000
|
9.000 |
12.000 |
16.00
|
Fan motor
|
kW
|
.590
|
.736
|
1.1
|
1.5
|
2.2
|
3
|
4
|
Static pressure
|
Pa
|
100
|
140
|
180
|
180
|
200
|
200
|
220
|
Out put cooling
|
kW
|
9.3
|
13.9
|
22
|
33.7
|
55.8
|
79
|
95.3
|
Pressure drop
|
Pa
|
31
|
20
|
22
|
25
|
33
|
41
|
41
|
Out put heating
|
kW
|
29
|
40.7
|
58.1
|
75.5
|
110.4
|
145.3
|
191.8
|
Pressure drop
|
Pa
|
22
|
14
|
16
|
18
|
27
|
32
|
34
|
|
|